| Rated operating voltage | AC/DC 690 V | 
| Rated operating current | 160 A | 
| Utilization category (switching mode) / AC 400 V | AC-23B | 
| Utilization category (switching mode) / AC 500 V | AC-22B | 
| Utilization category (switching mode) / AC 690 V | AC-22B | 
| Utilization category (switching mode) / DC 250 V | DC-21B | 
| Thermal current with fuse-link | 160 A | 
| Thermal current with disconnecting link ZP000 | 250 A | 
| Rated frequency | 40 ÷ 60 Hz | 
| Rated conditional short-circuit current (RMS) AC 400 V | 120 kA | 
| Rated conditional short-circuit current (RMS) AC 500 V | 50 kA | 
| Rated conditional short-circuit current (RMS) AC 690 V | 50 kA | 
| Rated impulse withstand voltage | 12 kV / FH00-.A/., 8 kV / FH00-.S/., 12 kV / FH00-3L/. | 
| Rated short-time withstand current | 5 kA | 
| Rated short-circuit making capacity / AC 400 V | 16 kA | 
| Rated insulation voltage | AC 1000 V | 
| Max. power losses of the fuse-link | 12 W | 
| Power losses without fuse-link / In | 7 W | 
| Degree of protection from front side, built-in device, cover opened | IP20 | 
| Degree of protection from front side, built-in device, cover closed | IP20 |